13’8″ x 18’4″ MODULAR CONCRETE GENERATOR ENCLOSURE – STORM RATED FEMA361/ICC500 DESIGN
MARKET CLASSIFICATION: PUBLIC SCHOOLS
APPLICATION
FEMA 361 – ICC500 Storm Rated Generator Building / Enclosure
QUANTITY MANUFACTURED
1
STANDARD FEATURES
- 6″ Steel Reinforced Concrete Walls and Roof Panel
- 8″ Waffle Profile Steel Reinforced Concrete Floor
- Each Panel Monolithically Poured
- Internal Structural Seals Protecting Structural Sealants from UV Exposure
- Duro-Last Roof Membrane Over Monolithic Concrete Roof Deck
- One (1) FEMA 361 Rated 3×7 Steel Door with Frames, FEMA 361 Rated Door Hardware, and Hydraulic Closer
- Form Finished Concrete Interior Walls Painted White
- Trowel Finished Concrete Floor Painted Gray
- 250mph Wind Rating
- 300psf Distributed Floor Load Rating
- 100psf Distributed Roof Load Rating
- ICC500 Large Missile Impact Rated/Tested Walls and Roof
CUSTOM INTEGRATION
- 100Amp Load Center 120/240VAC Single Phase – House Panel
- Four (4) Interior Fluorescent Light Fixtures
- Interior Emergency Lighting with Exit Sign
- Exterior Photocell Controlled Emergency Lighting with Battery Back-up
- Four (4) Convenience Receptacles on Walls
- Safety Signage
- 2,750 cfm Ventilation Fan on Thermostat Control, with Generator Run Relay and Large Missile Impacted Rated Exterior Hood
- FEMA 361 Rated Generator Ventilation Louvers
- ICC 500 Large Missile Impact Rated Generator Exhaust Port
- One (1) 10 Lbs. ABC Dry Chemical Fire Extinguisher
FOUNDATION TYPE
Helical Pier Foundation Designed for 250mph Wind Load to Customer Furnished Geotechnical Report
EXTERIOR DIMENSION
13’8″W x 18’4″L x 13’7″H
INTERIOR DIMENSION.
13’W x 17’4″L x 12’H
CUSTOM FEATURES
- Simulated Brick Exterior Finish with Custom Color Selection by Customer
- Custom Design to Manufacturer Specific Generator Specifications
SPECIAL INTEGRATION
Install Customer Furnished 275KW Diesel Generator, with 660 Gallon Belly Tank, Muffler, and Exhaust System Accessories
SPECIAL CERTIFICATIONS
- NPCA (National Precast Concrete Association) Plant Certification
- ICC500 Large Missile Impact Rating Certified Test Report for Walls, Roof, and Protective Hoods
- Vendor Furnished Materials Include Certified Impact and Wind Load Test Reports by the Original Equipment Manufacturer
- State Modular Building Design Approvals and Production Inspections